Chapter 14 Fault Codes and DescriptionsC2000 Plus
14-120
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
195
ASR AT process is too
short
(ATTv)
When using Explorer for ASR Auto Tune, the operated
process is too short for the drive to complete the
frequency bandwidth estimation.
Action and Reset
Action condition
The set number of turns is less than the minimum operation turn
Action time
N/A
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
Reset immediately
Record
Yes
Cause
Corrective Actions
The operation process is too short
for the drive to estimate
1. Increase torque command to increase the acceleration speed
2. Increase the operation travel

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)