Chapter 11 Summary of Parameter SettingsC2000 Plus 
 
11-11 
01 Basic Parameters 
 
Pr.  Parameter Name  Setting Range  Default  
 
01-00 
Maximum Operation 
Frequency 
0.00–599.00 Hz 
60.00 / 
50.00 
 
01-01 
Motor 1 Rated / Base 
Frequency  
0.00–599.00 Hz
 
60.00 / 
50.00 
 
01-02 
Motor 1 Rated / Base Output 
Voltage  
230V models: 0.0–255.0 V 
460V models: 0.0–510.0 V 
575V models: 0.0–637.0 V 
690V models: 0.0–765.0 V 
200.0 
400.0 
600.0 
660.0 
  01-03  Motor 1 Mid-Point Frequency 1    0.00–599.00 Hz  3.00 
 
01-04  Motor 1 Mid-Point Voltage 1   
230V models: 0.0–240.0 V 
460V models: 0.0–480.0 V 
575V models: 0.0–637.0 V 
690V models: 0.0–720.0 V 
11.0 
22.0 
0.0 
0.0 
  01-05  Motor 1 Mid-Point Frequency 2    0.00–599.00 Hz  1.50 
 
01-06  Motor 1 Mid-Point Voltage 2 
230V models: 0.0–240.0 V 
460V models: 0.0–480.0 V 
575V models: 0.0–637.0 V 
690V models: 0.0–720.0 V 
5.0 
10.0 
0.0 
0.0 
 01-07 
Motor 1 Minimum Output 
Frequency  
0.00–599.00 Hz  0.50 
 
01-08 
Motor 1 Minimum Output 
Voltage  
230V models: 0.0–240.0 V 
460V models: 0.0–480.0 V 
575V models: 0.0–637.0 V 
690V models: 0.0–720.0 V 
1.0 
2.0 
0.0 
0.0 
 01-09 Start-Up Frequency  0.00–599.00 Hz  0.50 
 
01-10  Output Frequency Upper Limit  0.00–599.00 Hz
  599.00 
 
01-11  Output Frequency Lower Limit  0.00–599.00 Hz
  0.00 
 
01-12 Acceleration Time 1 
Pr.01-45 = 0: 0.00–600.00 sec. 
Pr.01-45 = 1: 0.00–6000.0 sec. 
The default of motor drive with 30HP and above:   
60.00 / 60.0
 
10.00 
 
01-13 Deceleration Time 1 
Pr.01-45 = 0: 0.00–600.00 sec. 
Pr.01-45 = 1: 0.00–6000.0 sec. 
The default of motor drive with 30HP and above:   
60.00 / 60.0
 
10.00 
 
01-14 Acceleration Time 2 
Pr.01-45 = 0: 0.00–600.00 sec. 
Pr.01-45 = 1: 0.00–6000.0 sec. 
The default of motor drive with 30HP and above:   
60.00 / 60.0
 
10.00