Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-05-6
05-28
Accumulated Watt-Hour for a Running Motor (Wh)
Default: Read only
Settings 0.0–6553.5
05-29
Accumulated Kilowatt-Hour for a Running Motor (kWh)
Default: Read only
Settings 0.0–6553.5
05-30
Accumulated Megawatt-Hour for a Motor in High Word (MWh)
Default: Read only
Settings 0–65535
Pr.05-28–05-30 records the amount of power consumed by the motors. The accumulation begins
when the drive is activated and the record is saved when the drive stops or turns OFF. The amount
of consumed watts continues to accumulate when the drive is activated again. To clear the
accumulation, set Pr.00-02 as 5 to return the accumulation record to 0.
The accumulated total watts of the motor per hour = Pr.05-30 × 1000000 + Pr.05-29 × 1000 +
Pr.05-28 Wh
Example: When Pr.05-30 = 76 MWh and Pr.05-29 = 150 kWh, Pr.05-28 = 400 Wh (or 0.4 kWh),
the accumulated total kilowatts of the motor per hour = 76 × 1000000 + 150 × 1000 + 40 =
76150400 Wh = 76150.4 kWh
05-31
Accumulated Motor Running Time (Minutes)
Default: 0
Settings 0–1439
05-32
Accumulated Motor Running Time (Days)
Default: 0
Settings 0–65535
Use Pr.05-31 and Pr.05-32 to record the motor operation time. To clear the operation time, set
Pr.05-31 and Pr.05-32 as 00. An operation time shorter than 60 seconds is not recorded.
05-33
Induction Motor (IM) or Permanent Magnet Synchronous AC Motor (PM)
Selection
Default: 0
Settings
0: IM
1: SPM
2: IPM
3: SynRM
05-34
Full-Load Current for a Permanent Magnet Synchronous AC Motor /
Reluctance Motor
Default: Depending on the
model power
Settings Depending on the model power
Set the full-load current for the motor according to motor’s nameplate. The default is 90% of the
drive’s rated current.