Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-8
06-07
Over-Torque Detection Level (OT1)
Default: 120
Settings 10–250%
(100% corresponds to the rated current of the drive)
06-08
Over-Torque Detection Time (OT1)
Default: 0.1
Settings 0.0–60.0 sec.
06-10
Over-Torque Detection Level (OT2)
Default: 120
Settings 10–250%
(100% corresponds to the rated current of the drive)
06-11
Over-Torque Detection Time (OT2)
Default: 0.1
Settings 0.0–60.0 sec.
When the output current exceeds the over-torque detection level (Pr.06-07 or Pr.06-10) and
exceeds the over-torque detection time (Pr.06-08 or Pr.06-11), the over-torque detection follows
the setting of Pr.06-06 and Pr.06-09.
When you set Pr.06-06 or Pr.06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running after over-torque detection. The warning remains on until the output current is smaller
than 5% of the over-torque detection level.
When you set Pr.06-06 or Pr.06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops
running after over-torque detection. The drive does not run until you manually reset it.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals