Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-7
This is a protection for the drive to decrease output frequency automatically when the motor over-
loads abruptly during constant motor operation.
If the output current exceeds the setting value for Pr.06-04 when the drive is operating, the drive
decelerates according to the Pr.06-05 setting to prevent the motor from stalling. The lower limit for
the over-current stall prevention is determined by the maximum value among 0.5 Hz, Pr.01-07 and
Pr.01-11.
If the output current is lower than the setting value for Pr.06-04, the drive accelerates (according
to Pr.06-05) again to the setting frequency.
06-05
Acceleration / Deceleration Time Selection for Stall Prevention at Constant
Speed
Default: 0
Settings 0: By current acceleration / deceleration time
1: By the first acceleration / deceleration time
2: By the second acceleration / deceleration time
3: By the third acceleration / deceleration time
4: By the fourth acceleration / deceleration time
5: By Auto-acceleration / auto-deceleration
Set the acceleration / deceleration time selection when stall prevention occurs at constant speed.
06-06
Over-Torque Detection Selection (OT1)
06-09
Over-Torque Detection Selection (OT2)
Default: 0
Settings
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
When you set Pr.06-06 and Pr.06-09 to 1 or 3, a warning message displays, but there is no error
record.
When you set Pr.06-06 and Pr.06-09 to 2 or 4, an error message displays and there is an error
record.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)