Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-09-9
09-91
Additional Settings for the Communication Card (for EtherNet)
Default: 0
Settings bit0: Enable IP filter
bit1: Enable internet parameters (1 bit).
When the IP address is set, this bit is enabled. After updating the
parameters for the communication card, this bit changes to disabled.
bit2: Enable login password (1 bit).
When you enter the login password, this bit is enabled.
A
fter updating the
parameters for the communication card, this bit changes to disabled.
09-92
Communication Card Status (for EtherNet)
Default: 0
Settings bit0: Enable password
When the communication card is set with a password, this bit is enabled.
When the password is cleared, this bit is disabled.