Chapter 12 Description of Parameter SettingsC2000 Plus
12.2-34
Basic motor parameters adjustment
1. Parameter reset:
Reset Pr.00-02=9 (50Hz) or 10 (60Hz) to the default value.
2. Select IPM motor type:
Pr.05-33=2 (IPM)
3. Motor nameplate parameter setting:
Parameter Description
Pr.01-01
Motor 1 Rated / Base Frequency (Hz)
Pr.01-02
Motor 1 Rated / Base Output Voltage (V
AC
)
Pr.05-33 PM motor type (IPM or SPM)
Pr.05-34 Rated current (A)
Pr.05-35 Rated power (kW)
Pr.05-36 Rated rotor speed (RPM)
Pr.05-37 Number of poles for the motor (poles)
4. PM parameter auto-tuning:
Set Pr.05-00 = 5 (rolling auto-tuning for PM, with no load) or 13 (static auto-tuning for PM)
and press RUN key to finish motor auto-tuning, then you will get the following parameters:
Parameter Description
Pr.05-39
Stator resistance for a permanent magnet motor (
Ω)
Pr.05-40 Permanent magnet motor Ld (mH)
Pr.05-41 Permanent magnet motor Lq (mH)
Pr.05-43
Ke parameter of a permanent magnet motor (V
phase
rms
/ krpm)
(When Pr.05-00=5, the Ke parameter is measured based on the actual
motor rotation.)
(When Pr.05-00=13, the Ke parameter is automatically calculated
based on the motor power, current and rotor speed.)
If an auto-tuning error (AUE) occurs, refer to Chapter 14 “Fault Codes and Descriptions” for
further treatment.
AUE Error (code) Description
AUE (40) Auto-tuning error
AUE1 (142) Auto-tuning error 1 (No feedback current error)
AUE2 (143) Auto-tuning error 2 (Motor phase loss error)
AUE3 (144) Auto-tuning error 3 (No-load current I
0
measuring error)
AUE4 (148)
Auto-tuning error 4 (Leakage inductance Lsigma measuring
error)
5. Set control mode
Control mode for the drive: Pr. 00-10 = 0: Speed mode
Control mode for the motor: Pr. 00-11 = 7: Interior PM FOC Sensorless
6. After auto-tuning, cycle the power.
7. Measure the initial magnetic pole angle of PM
When Pr.00-11=7 PM FOC Sensoreless mode, the initial magnetic pole angle detection
method is high frequency injection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)