Chapter 13 Warning CodesC2000 Plus
13-97
ID No. Display on LCD Keypad Warning Name Description
131
Posn Overflow (PoF)
When the position record is bigger than the setting
range at Pr.11-75.
Action and Reset
Action condition Verify if the current position is over the setting range at Pr.11-75.
Action time Immediately acts
Warning Setting Parameter N/A
Reset method Stop running the motor drive, then manual reset.
Reset condition Immediately resets
Record N/A
Cause Corrective Actions
Homing process incomplete Verify if the homing process is completed.
Position record is bigger than the
setting range at Pr.11-75
Verify if the current position is over the upper and lower limit of Pr.11-75.