Chapter 14 Fault Codes and DescriptionsC2000 Plus
14-16
ID* Display on LCD Keypad Fault Name Fault Descriptions
12
Low-voltage during
deceleration
(Lvd)
DC bus voltage is lower than Pr.06-00 setting value
during deceleration
Action and Reset
Action condition Pr.06-00 (Default = depending on the model)
Action time Act immediately when DC bus voltage is lower than Pr.06-00
Fault treatment parameter NA
Reset method Manual reset
Reset condition
Reset when DC bus voltage is higher than Pr.06-00 + 30V (Frame A
D) / 40V
(Frame E and above)
Record Yes
Cause Corrective Actions
Power-off Improve power supply condition.
Power voltage changes Adjust voltage to the power range of the drive.
Start up the motor with large
capacity
Check the power system.
Increase the capacity of power equipment.
Sudden load
Reduce the load.
Increase the drive capacity.
DC bus Install DC reactor(s).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals