Chapter 14 Fault Codes and DescriptionsC2000 Plus
14-65
ID* Display on LCD Keypad Fault Name Fault Descriptions
63
Over slip error (oSL)
On the basis of the maximum slip limit set via Pr.10-
29,
the speed deviation is abnormal. When the motor drive
outputs at constant speed, F>H or F<H exceeds the level
set via Pr.07-29, and it exceeds the time set via Pr.07-
30, oSL shows. oSL occurs in induction motors only.
Action and Reset
Action condition
Pr.07-29
100% of Pr.07-29 = the maximum limit of the slip frequency (Pr.10-29)
Action time Pr.07-30
Fault treatment parameter
Pr.07-31
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset method
Auto
Pr.07-31 = 0 is a warning.
When the motor drive outputs at constant speed, and F > H or F <
H
does not exceed the level set via Pr.07-
29 anymore, oSL warning will
be cleared automatically.
Hand When Pr.07-31 = 1 or 2, oSL is an error, and it needs to reset manually.
Reset condition Reset immediately
Record Pr.07-31 = 1 or 2, oSL is Fault, and will be recorded.
Cause Corrective Actions
Any of the motor parameters in
parameter group 5 may be
incorrect
Check the motor parameters
Overload Decrease the load
Any of the setting value of Pr. 07-
29, 07-30, and 10-29 is improper
Check the setting of oSL protection function related parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals