102
Pre Turn-off Warnings
1. Before you perform the turn-off procedures, please make sure the critical loads
connected to the UPS have already been safely shut down.
2. Please follow the turn-off procedures for each of the operation modes to shut down
the UPS and make sure the Output Switch (Q4) is the last one to be turned off.
Otherwise, it may cause abnormalities or damage to the unit.
6.2 Start-up Procedures
6.2.1 On-Line Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read
6.1 Pre Start-up & Pre Turn-off Warnings
thoroughly and ensure that the precautions and instructions have been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the
OFF
position.
Step 2
Switch
ON
every external battery cabinet’s breaker (Q5).
Step 3
Switch
ON
the Output Switch (Q4).
Step 4
Switch
ON
the Input Switch (Q1) and Bypass Switch (Q2).
Step 5
Tap the
ON/ OFF Button
( ) on the LCD screen.
Step 6
After the inverter turns on, the UPS will run in On-Line mode, the LCD screen will show as
below, and the tri-color LED indicator will illuminate green.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DPS Series and is the answer not in the manual?

Delta DPS Series Specifications

General IconGeneral
Frequency50/60 Hz
Battery TypeSealed Lead-Acid (SLA)
Communication InterfaceRS-232, USB, SNMP (Optional)
Output Voltage220/230/240VAC
TopologyDouble Conversion
Form FactorTower or Rackmount
Power Factor0.9
TypeOnline UPS
Protection FeaturesShort Circuit

Related product manuals