Ultron DPS Series
106
From Manual Bypass Mode to On-Line Mode
Step 1
Switch
ON
every external battery cabinet’s breaker (Q5).
Step 2
Switch
ON
the Output Switch (Q4).
Step 3
Switch
ON
the Input Switch (Q1) and Bypass Switch (Q2).
Step 4
Switch
OFF
the Manual Bypass Switch (Q3).
Step 5
Tap the
ON/ OFF Button
( ) on the LCD screen.
Step 6
After the inverter turns on, the UPS will run in On-Line mode, the LCD screen will show as
below, and the tri-color LED indicator will illuminate green.