Item Sub Item Description
SENSOR
ID
Set the ID # (ID 0/ ID 1/ …/ ID 15) according to the ID DIP
switch setting of the EMS 1000 (EnviroProbe) device.
NOTE:
If the ID # setting is wrong, the warning message
'
The EMS 1000 ID # Communication Fail
' will
appear.
Title
Set the title for the EMS 1000 (EnviroProbe), 16 characters
at most.
Status
The status ‘
Enable/ Disable
’ determines whether or not
the LCD shows the EMS information of the EMS 1000
(EnviroProbe) device (ID #).
Temperature
Set the temperature (°C) values for Alarm/ Warning/
Recovery.
Humidity Set the Humidity (%) values for Alarm/ Warning/ Recovery.
INPUT
CONTACT
Input Contact 1 1. Set the input contact as Normally Open (NO)/
Normally Closed (NC).
2. Set the Title for the input contact, 16 characters at
most.
3. Set the Event Type as None/ Information/ Warning/
Alarm.
Input Contact 2
Input Contact 3
Input Contact 4