10
Amplon N Series
3.2 Multi-function Buttons
No.
Multi-
function
Button
Description
1
The button has two functions. Please refer to the following for
detailed information.
1. Buzzer On/ Off:
When the buzzer is on, press the button for 0.1 second to
turn off the buzzer. When the buzzer is off, press the button
for 0.1 second to turn on the buzzer.
&RQ¿UPDWLRQ
In setup mode, press the button for 0.1 second to enter into
WKHLWHPWKDW\RXZDQWWRVHWXSRUFRQ¿UP\RXUSDUDPHWHU
setup.
2
ON
The button has three functions. Please refer to the following for
detailed information.
1. Turn-on:
z
In bypass mode, press and hold the button for 3 seconds,
release it after you hear one beep and the UPS will run in
on-line mode.
z
Cold start: When there is no AC input, press and hold the
button for 3 seconds, release it after you hear one beep
and the UPS will start up in battery mode.
2. Battery Test:
z
A battery test can only be executed in on-line mode.
z
For manual battery test, please press and hold the button
for 3 seconds, release it after you hear one beep, and the
UPS will transfer to run in battery mode and perform a
10-second battery test. If the test result is ok, the 7-seg-
ment display will show ‘PAS’ and the UPS will return to
on-line mode. If the test result is abnormal, the 7-segment
display will show ‘FAL’, the no-battery/ battery replace-
ment icon (
) will illuminate and the UPS will return to
on-line mode. For 7-segment display information, please
refer to 6HJPHQW'LVSOD\.