Chapter 8 Alarm
41
Chapter 8 : Alarm
When the external battery pack connected to the UPS has the following problems,
the UPS system will sound an alarm. Please see the table below.
No. Condition Alarm
1 Battery Mode Sounds once every 2 seconds.
2 Low Battery Sounds once every 0.5 second.
3
Battery Missing/ Weak Battery
Battery Replacement *
Sounds once every 2 seconds.
4 Overload
2YHUORDGBa7KHDODUP
sounds once every 2 seconds.
2YHUORDGBa7KHDODUP
sounds once every 0.5 seconds.
5 Fault
The alarm sounds continuously for 5
seconds when the UPS detects an
internal fault. After the 5 seconds, the
alarm sounds once every 2 seconds.
NOTE :
* : After reconnecting or replacing the batteries, it might take a while for the
UPS to switch off the alarm automatically. If, after a period of time, the audible
alarm still exists, the user must manually initiate a battery test (press
and
hold the
ON
button for 3 seconds and release it after you hear one beep) to
clear the alarm.