4-20
Control mode VF FOCPG FOCPM
Factory default: 80
Settings 0~1000ms
Ramp the flow value for the flow command so as to reduce the vibration of the machine.
Set the time required for ramping the flow from 0~the maximum flow (01-02).
00-31 00-3
Time
Flow command
given to
controller
Flow command
after driver
processing
a
Valve opening delay time
Control mode VF FOCPG FOCPM
Factory default: 0
Settings 0 – 200ms
When both the pressure command and flow command activate the machine to start from idle, the
flow starts to output. However, due to the slower response of the valve in the
hydraulic circuit, the
sudden surge of the pressure may occur. The pressure may recover to normal till the valve is fully
opened.
To avoid the aforementioned effect, set this parameter to increase time for the flow output
delay.
Parameter 00-33
Pressure
Command
Flow
Command
Before pressure
feedback adjustment
After pressure
feedback adjustment
Before flow feedback
adjustment
After flow feedback
adjustment
Reserved
a
Over-pressure detection level
Control mode VF FOCPG FOCPM
Factory default: 230
Settings 0~250 Bar
When the pressure feedback exceeds this parameter setting, an “ovP over pressure” error
message may occur.
a
Detection of disconnection of pressure feedback
Control mode VF FOCPG FOCPM
Factory default: 0
Settings 0: No function