4. Description of Parameters
4-37
Control mode VF FOCPG FOCPM
Factory default: 0
Settings 0: F (frequency command)
1: H (actual frequency)
2: Multi-function display (user-defined 00-04)
3: A (Output current)
This parameter is used to set the contents of the start-up screen. The content of the user-defined
option is displayed in accordance with the setting value of Parameter 00-04.
a
Slave reverse operation for depressurization
Control mode VF FOCPG FOCPM
Factory default: 0
Settings 0: Disabled
1: Enabled
This parameter setting is required only for the Slave but not needed for the Master.
When the parameter is set as 1, it is necessary to make sure that the outlet end of the Slave is not
installed with any one-way valve and the parameter 03-16 is set as 500.