EasyManua.ls Logo

Design Analysis H-522 - Chapter 18 4 To 20 Milliamp Output; 18.3 4 To 20 Milliamp Options

Default Icon
272 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 18
4 To 20 Milliamp Output
XL™ Series 4 To 20 Milliamp Output 18-1
18.1 Introduction
These options allow the XL™ to use any of its input signals as a data source to generate a current
output simulating a 4 to 20 mA sensor. The XL does not actually generate the current in the loop
but controls the current in a loop that is externally powered. The 4 to 20 milliamp connection
points are optically isolated from the rest of the XL circuitry.
18.2 4 To 20 Milliamp Menus
Built in Menu Structure: 4 to 20 Milliamp Options Menu.
Output Options -> 4-20 mA Options -> mA Output = X.XXX
4-20 Source [None ]
Max Value [20.00 ]
Min Value [0.00 ]
PC Menu Screen: 4 To 20 Milliamp Options.
4 to 20 MilliAmp Output Options (Esc to Return)
Current Milliamp Output: Not Enabled
S - Data Source: None
H - Maximum Level: 20.000
L - Minimum Level: 4.000
Enter Option >
18.3 4 To 20 Milliamp Options
PC Interface View Built In Display Screen
Current Milliamp Output: xx.xx
mA Output = XX.XX
This screen shows what the output current should be if it were measured with a current meter. It
should be in the range of 4 to 20 milliamps. This is based on the value of the data source, the
Max value and the Min value.
If a current meter is used to verify the output and it does not match this value then check the