24
Weight and Measures Specification : To enter this mode, enter the numeric keys 1,4,2
while pressing the Rezero Key. The Span Switch must be “ON” to enter this mode.
Spec No. Bit 3 Bit 2 Bit 1 Bit 0
20 Minimum Display ( Scale 1)
00 : 2 10 : 5
01 : 1 11 : 10
Minimum Display (Scale 2)
00 : 2 10 : 5
01 : 1 11 : 10
21 Not used Weight Decimal Point Position (Scale 1)
000 : 00000 011 : 00.000
001 : 0000.0 100 : 0.0000
010 : 000.00
22 Not used Weight Decimal Point Position (Scale 2)
000 : 00000 011 : 00.000
001 : 0000.0 100 : 0.0000
010 : 000.00
23 Display Resolution
00 : 1/10,000 10 : 1/2,500
01 : 1/5,000 11 : Not Used
Zero Setting Range
00 : Unlimited 10 : +- 10% FS
01 : +- 2% FS 11 : Not Avail.
24 Masked Display
at Minus Wt.
0 : Gross
1 : Net
Display at
Minus Wt.
0 :Minus
Display
1 :Masked
Zero Lamp
Lighting
Method
0 : Gross
1 : Net
Display Mask When
Battery Low
0 : Yes
1 : No
25 Scale Starting
Method
0 : Automatic
1 : Manual
IR Mode
protected by
Span Switch
0 : No
1 : Yes
Scale Type
0 : Single
Scale
1 : Double
Scale
Gross Mode
Available
0 : Yes
1 : No
26 Zero Tracking
When Tare
0 : Yes
1 : No
Weight Reset
when Tare
0 : Yes
1 : No
Initial Start Range
00 : Unlimited 10 : +- 10% FS
01 : +- 2% FS 11 : Not Avail.
27 Comma Dis
la
0 : No
1 : Yes
Digital Tare
Setting
0 : No
1 : Yes
Tare Range
00 : 100%FS 10 : 5% FS
01 : 50%FS 11 : Not Available
28 Auto Tare clear
when Rezero
0 : No
1 : Yes
Automatic Unit Weight Clear
Condition
00 : Over Net 5d and Gross 21d
and Weight Stable
01 : >= Net 1d and Weight Stable
10 : >= Net 1d and Quantity >0
and Weight Stable
Automatic Unit
Weight Clear
0 : No
1 : Yes
29 Di
ital Tare
Rounding
0 : Tare
Exactly
1 : Round to
Nearest
Increment
Tare Value
Exchange
0 : Yes
1 : No
Tare Addition
0 : Yes
1 : No
Tare Subtraction
0 : Yes
1 : No