34 734N Installation and Programming Guide | Digital Monitoring Products, Inc.
COMPLIANCE LISTING SPECIFICATIONS
UL ACCESS CONTROL
The access relay must be configured as fail-safe or fail-secure as determined by the local Authority
Having Jurisdiction (AHJ). This system is not intended to be used in place of listed panic hardware.
For listed installations, the 734N or 734N-POE must be installed within the protected area.
The power supply must be a listed commercial burglary/household fire, power limited, Class 2 with
a compatible voltage range for the product. The 734N requires a 12 or 24 VDC power source. The
734N-POE can be powered by a 12 or 24 VDC or UL 294 listed POE switch.
For listed installations, the 734N-POE must be installed inside a UL listed DMP metal enclosure such
as a Model350. Refer to Mount the Device for mounting instructions.
Allow 4 hours for standby power to meet UL listed standards.
ULC COMMERCIAL BURGLARY (XR150/XR550 SERIES PANELS)
When using the zones of the 734N in a listed application, place the module in a listed enclosure and
connect a DMP Model 307 Clip-on Tamper Switch to the enclosure programmed as a 24-Hour zone.
The 734N Access Control features have not been investigated by ULC.
The 734N zones can be used in a Low Risk application. For Medium or High Risk applications, refer to
the Dual Zone Protection diagram in the XR150/XR550 Canadian installation guide.

Other manuals for DMP Electronics 734N

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics 734N and is the answer not in the manual?

DMP Electronics 734N Specifications

General IconGeneral
BrandDMP Electronics
Model734N
CategoryControl Unit
LanguageEnglish

Related product manuals