REFRIGERANT LOW
LOW SIDE PRESSURE
L
IM
I
T(Optional)
ThePLCwillimmediatelyacknowledgeanopencircuitifthelowpressureswitchistrippedanddeenergizethecompressor.Itwill
recordanddisplaylowpressurefaultonthealarmscreen.IfthePLC detectsalowpressurefaultduringoperation,aLPfaultwillbe
displayedandrecorded.
ThePLCwillnotallo wthecompressorrelaytobereenergized,untilswitchisintheclosedposition.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenabling thesystemorstage.
ANALOGINPUTS
HIGH LIMIT
T
E
M
P
ERA
TU
RESETPOINT
ThehighlimittemperaturesensoriscontinuouslymonitoredwhetherinCooling,ReverseCycleorElectricHeatmode.
Thissensorisusedtodetectahightemperatureconditioninthesupplywaterfromthechiller.Ifthech illedwatertemperatureissensed
tobegreaterorequalto125°F(51.7°C),allenabledcompressorrelayswillbedeenergized,turningoffthecompressor(s)ifoperating
inreversecyclemode.If
electricheatisbeingused,allenabledheaterrelayswillbedeenergized,turningofftheheatingelement(s).
Asthetemperaturefalls,thecompressororelectricheatrelaywillreenergizewhenthetemperaturereaches110°F(43.3°C).
Ahightemperaturefaultwillberecordedanddisplayedifthesystemexceeds
thealarmsetpoint.Inahightemperaturesituation,PLC
willnotallowthecompressororelectricheatrelaytobeenergized.Thefaultmustbemanuallyacknowledgedontheactivealarm
screenandclea redpriortoreenablingthesystemorstage.
Ifatemperaturesensorisbadornotconnected,thePLCwilldisplayanalarmforthatsensor.
FREEZE
T
EM
P
E
R
A
T
U
RESETPOINT
ThelowlimittemperaturesensoriscontinuouslymonitoredwhetherinCooling,ReverseCycleorElectricHeatmode.
Thissensorisusedtodetectafreezeconditioninthesu pplywaterofthechiller.Ifthechilledwatertemperatureissensedtobeequalto
or less than38°F(3.3°C),thenthe compressor relaywill be deenergized,shuttingoff thecompressor. As the temperature rises, the
compressorrelaywillreenergizewhenthetemperaturereaches42°F(5.6°C).
Alowtemperaturefaultwillberecordedanddisplayedifthesystemfallsbelowthealarmsetpoint.Inalowtemperaturesituation,
PLCwillnotallowthecompressororelectricheatrelaytobeenergized.Thefaultmustbemanually
acknowledgedontheactivealarm
screenandcleare dpriortoreenablingthesystemorstage.
Ifatemperaturesensorisbadornotconnected,thePLCwilldisplayanalarmforthatsensor.
CondenserFreezeProtection(Optional)
Thesystemisequippedwithatemperaturesensormountedtothecondensercoil.Thissensoristheretosensethecoiltemperature.In
heatmodeifthecoiltemperaturedropsbelow40°F,thePLCcontrolswillautomaticallylowerthespeedofthecompressortohalfthe
speedthatitwas
currentlyrunning.Thedisplaywillindicate“FreezeDefrost”whileperformingthisoperation.
PRESSURE
TR
AN
SD
UCERS
SUCTION Pressure
ThesuctionpressureiscontinuouslymonitoredbythePLC.Ifthesuctionpressureisbelowthealarmsetpointforlongerthanthe
programmedtimedelay,afaultwilloccur .Thislowsuctionfaultwillberecordedanddisplayedonthealarmscreen.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenablingthesystemorstage.
DISCHARGE Pressure
ThedischargepressureiscontinuouslymonitoredbythePLC.Ifthedischargepressureisabovethealarmsetpointforlongerthanthe
programmedtime,afaultwilloccur.Thishighpressurefaultwillberecordedanddisplayedonthealarmscreen.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenablingthesystemorstage.
