6
RELAYOUTPUTS
COMP
C
OMPR
E
SSOR
PLCCOMPoutputwillprovideswitchedpowertothecontactorcoiltoenablethecompressornormaloperation.
CWP
CHILL WATER
P
UM
P
PLCCWPoutputwillprovideswitchedpowertothecontactorcoilsforthechilledwaterpump.
SWP
SEA WATER
P
UM
P
PLCSWPoutputwillprovideswitchedpowertothecontactorcoilsfortheseawaterpump.
RV
REVERSING
VAL
VE
PLCRVoutputwillprovideswitchedpowertothecoilsforthereversingvalve.
EH
ELECTRIC
H
EA
T
PLCEHoutputwillprovideswitchedpowertothecontactorcoilsfortheelectricheat.
F
AULT
Provid esaNormallyOpen(NO)contactpoint.AnyfaultconditionwillclosetheNOcontact.Thisoutputcanbeusedtopoweralight,
relay,orinterfacetoaship’smonitoringsystem.Theoutputonthisterminalwillbe230VAC.
SYSTEM
OVERVIE
W
SYSTEM
P
OWER
UP
SOFTWARE REVI
S
I
O
N
Uponapplyingpowertothesystem,thedisplaywillindicatethesoftwarerevisionnumberordisplayitonthemainstatus
screen.
PLCisenabledandwaitingforuserselection.
MODBUS
ThePLCcomeswitha3wireModbusconnectionaspartoftheelectricalbox.Thisconnectionisusedformultistageconfigurationand
networkingtoaboatmanagementsystem.
S
TA
RT
UP
ThePLCChillercontrollercanbeoperatedasasingleoramultistagechillerplant.Duringinitialsetup,thesystemwillbeconfiguredfor
thenumberofstagesandtheavailableoptions.SelectbetweenReturnwaterorSupplywatercontrol.Theuserhastheoptiontoselect
betweenmetricvalues
beingdisplayedorImperialvaluesbeingdisplayedduringoperationofthesystem.
ChilledwatersetpointwillbeenteredforCoolandHeatmode.
Onceenabled,CWandSWpumpswillbeturnedonforoperation.
OPERATIONAL
CHECK
S
OncethePLCisenabledthesystemwillconductprestartupchecks.ThePLCprogramwillcheckallCWflowswitchesforfaults.ThePLC
willalsocheckHPandLPswitchesforfaults.
Individualstagefaultswillonlydisablethatstage.
S
ET
POI
N
T
S
C
OO
LI
N
G
CoolingsetpointisanadjustableparameterforReturncontrol(default)from48°F(8°C)to58°F(14°C)inonedegreeincrementsandfor
Supplycontrolfrom42°F(5°C)to58°F(14°C).Toadjustthecoolingsetpoint,simplytouchthe PLCscreenandchangetodesirednewset
point.Incooling
modeyouwillnotbeabletoenteranumberoutsideofthisrange.