7
H
EATING
Heatingsetpointisanadjustableparameterfrom95°F(35°C)to120°F(49°C)inonedegreeincrements,forbothReturn&Supply
control.Toadjusttheheatingsetpoint,simplytouchthePLCscreenandchangetodesirednewsetpoint.Inheatingmodeyouwillnot
beabletoenteranumberoutsideofthisrange.
C
OMPRESSOR
S
TAGING
T
IM
E
CompressorstagingtimeisaPLCadjustableparameterfrom10secondsto110secondsin10secondincrements.Toadjustthestaging
time,simplytouchthePLCscreenandchangetodesirednewsetpoint.Userwillnotbeabletoentera numberoutsideofthisrange.
OncethePLCinitiatesacoolingcycle,thestagingtimeisthetimeitwilltake(inseconds)forthenextcompressorrelaytoclose.
RUN MODE
C
OOL
ING
Compressorrotationisactiveduringrunmode.Thecompressorwiththelowestrunninghourswillbeenabledfirstandcompressorwith
thehighestrunninghourswillbedisabledfirst.
Firststag ewillbeenabledandthecompressorwillstartafterCWandSWflowsarestablefor10seconds(default).
Firststagewillcontinuetorunfor1minutebeforeenablingthenextstage.Ifthelooprequiresdemand,thenthenextstagewillbe
enabled.
R
UN
M
ODE
R
EVERSE
C
YCLE
H
EA
TI
NG
Compressorrotationisactiveduringrunmode.Thecompressorwiththelowestrunninghourswillbeenabledfirstandcompressorwith
thehighestrunninghourswillbedisabledfirst.
EnableReverseCycleHeatonlyforthesystem.
Firststag eheatingwillbeenabledandthecompressorwillstartafterCWandSWflowsarestablefor10seconds.
Firststagewillcontinuetorunfor5minutesbeforeenablingthenextheaterstage.Ifthelooprequiresdemand,thenthenextstagewill
beenabled.
R
UN
M
ODE
E
LECTRIC
H
EAT
I
N
G(optionalheaterbarrel)
Heaterrotationisactiveduringrunmode.Theheaterwiththelowestrunninghourswillbeenabledfirstandtheheaterwiththehighest
runninghourswillbedisabledfirst.
EnableElectricHeatonlyforthesystem.
Firststag ewillbeenabledandtheelectricheaterwillstartafterCWflow
isstablefor10seconds.
Firststag ewillcontinuetorunfor5minutesbeforeenablingthenextheaterst age.IfthePIDlooprequiresdemandthenthenex t
stagewillbeenabled.
OPERATIONAL
M
ODES
PUMP
O
PE
RA
TI
O
N
CHILLED WATER
P
UM
P
Thechilledwaterpumprelayshallcloseifthesystemisinheatmodeorcoolmode.Thepumpwillbeenabled5secondpriortothe
firststagebeingenabled.Pumpwillbeonforcontinuousoperationwhensystemisenabled
SEA WATER
P
UM
P
Theseawaterpumpwillhaveaselectableoperatingmodebetweencontinuousoperationorcyclewithcompressoroperation.
Thedefaultconfigurationistocyclewiththedemand.
Theseawaterpumprelayshallclose5secondsbeforethecompressorstartsinheatingorcoolingmodesandwillopen5seconds
afterthelas tcompressorcycleiscompleted.Ifimmersionheatingisavailableandused,theseawaterpumpwillbedisabled.
Inamultistage configurationthepumpoutputs
canbedaisychainedatthebackoftheunittosupplypowertothepumps.
Thiswillallowanystagetosu pplypowertothepumpswhenbein gstagedonandoffandasaredundantcontrolforthepumps.


Related product manuals