Mounting
Fig. 73
Accessories may include, e. g.:
sensors, operating mode switch, emergency open/stop button, key switch, locking
device, battery pack, manual release, door status signal, locking request,
synchronization cable
Note
The battery pack only reaches its full capacity after 12 hours of
charging time. The battery pack must be fully charged to ensure
emergency operation.
Mount and connect the accessories according t o the accompanying m anuals. Holes
in the opera tor profile m ust be drilled with a d
IAMETER OF
8 mm.
4.24 Position the sensors
Note
Only sensors with a valid type approval according to EN 16005 may
be used.
Note
The use of light barriers to secure the passage area of sliding doors
does not conform to EN 16005.
The size of the detection field depends on the mounting height and the settings of
the sensor (see sensor manual). According to EN 16005, the test piece CA must be
detected anywhere in the sliding door’s passage area. The size of the detection
zone depends on the mounting height and the settings of the sensor (see sensor
manual). The sensors’ detection zone is to be set in such a way t h at the doors do
not run into the test object.
Large opening widths may require several sensors.