Fire protection function
9 Fire protection function
The fire protection function enables the sliding door to close safely in case of fire.
The function is controlled externally, e.g. via fire alarm systems or building
management systems. A rechargeable battery is required for the function.
1. Activate the fire protection function
1. Connect the external control unit for the fire protection function t o the
multiport or the I/O.
2. Activate the fire protection function via the "P" parameter.
3. Configure the multiport for fire protection
When the parameter " P" is set to the fire protection function, the following
functions/parameters are changed:
can be changed
subsequently
is changed toParameter
yes5Obstacles in Open
yes5Obstacles in Closed
yesDoor stopsBlocking function
noEdgeNight/bank configuration
no
Emergency
operation
Battery mode
nois ignoredPower saving mode
no5 seconds
Waiting time at the obstacle in closing
direction
When the fire protection function is triggered, the door closes and is locked.
The door moves at creep speed due to the deactivated sensor system.
The following functions are no longer possible:
• Opening the door via the sensor system
• Change of the operating mode
Opening the door is now only possible via the night/bank impulse.