PowerSeries - PC1616/PC1832/PC1864
58
Appendix C: SIA False Alarm Reduction
SIA Feature
Programming Section
Comments Range/Default Requirement
Exit Time - [005], 3rd entry
Access to Entry and Exit delays for each partition and Bell Time Out for the system For Full or auto arming:
Range:
45-255 seconds
Default:
60 sec.
Required
(programmable)
Progress Annunciation/
Disable - for Silent Exit -
[014], Option 6 ON
Enables audible exit beeps from the keypad for the duration of exit delay Individual keypads
may be disabled
Default:
All Enabled
Allowed
Exit Time Restart -
[018], Option 7 ON
Enables the exit delay restart feature
Default:
Enabled Required
Auto Stay Arm on Unvacated
Premises - [001]-[004] Zone
type 05, 06
Function Key: Stay Arming. All Stay/Away type zones (05, 06) will be automatically
bypassed
If no exit after full arm
Default:
Enabled
Required
Exit Time and Progress
Annunciation/Disable
or Remote Arming -
[005] and [014] bit 6
System Times and Audible Exit beeps can be disabled when using the Key fob to
arm away the system
Default:
Enabled Allowed
Entry Delay(s) - [005], 1st and
2nd entry
Access to Entry and Exit delays for each partition and Bell Time Out for the system.
NOTE:
Combined Entry delay and Communications Delay (Abort Window) shall not
exceed 60s
Range:
30 sec. to 4 min.
Default:
30 sec.
Required
(programmable)
Abort Window for Non-Fire
zones - [101]-[164] bit 7 ON
Access to zone attributes, i.e, swinger shutdown, transmission delay and cross
zone. Individual zones attribute bit 7 (Transmission delay) is by default ON
May be disabled
by zone or zone type
Default:
Enabled
Required
Abort Window - for Non-Fire
zones - [377], 4th entry
Access to the programmable delay before communicating alarms.
NOTE:
Com
-
bined Entry delay and Communications Delay (Abort Window) shall not exceed 60s
Range:
15 - 45 sec.
Default:
30 sec.
Required
(programmable)
Abort Annunciation - [382],
Option 3 ON
Enables the “Communication Cancelled” message display on all keypads Annunciate that no
alarm was transmitted
Default:
Enabled
Required
Cancel Annunciation - [328],
8th entry
Access to the reporting code for Alarm Cancelled Annunciate that a
Cancel was transmitted
Default:
Enabled
Required
Duress Feature - [
][5] Master
Code - [99] Option 2 ON
Do not derive code from an existing Master/User code (e.g., Master code is 1234,
the duress code should not be 1233 or 1235)
No 1+/- derivative of another
user code. No duplicates with
other user codes
Default:
disabled
Allowed
Cross Zoning - [018]
Option 6 ON
[101]-[164] bit 9 OFF
This option enables Cross Zoning for entire system. Individual zones can be ena
-
bled for Cross zoning via Zone attribute bit 9 in sections [101] - [164]
Programming required
Default:
Disabled
Required
Cross Zone Timer - [176]
Access to the programmable Cross Zone timer May program
Range: 001-255 sec.
Default:
60 secs
Allowed
Swinger Shutdown for Alarms
[377] 1st entry
Access to the swinger shutdown limit for zone alarms For all non-fire zones
shut down at 1 or 2 trips
Default:
1 Trip
Required
(programmable)
Swinger Shutdown Disable -
[101] - [164] bit 6 ON
Access to zone attributes, i.e., swinger shutdown, transmission delay and cross
zone. Individual zones attribute bit 6 (Swinger shutdown enabled) is by default ON
For non-police
response zones
Default:
Enabled
Allowed
Fire Alarm Verification -
Zone Type [29]
Auto Verified Fire, use only with 4 wire type detectors that can be reset by the panel
4-wire smoke detector powered from AUX + and PGM1 - PGM4 (type 03, Sensor
reset)
70 seconds reset and
confirmation time
Default:
disabled
Required
Call Waiting Cancel Dial String -
[304], [382], Opt. 4 OFF
Access to the dialing sequence used to disable call waiting Dependant on user phone line
Default:
disabled
Required
Testing
System Test: [
][6] Master
Code, Option 4
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.
Refer to the User Manual (part no. 29008261).
Installer Walk Test Mode: [901]
This mode is used to test each zone on the system for proper functionality.
Alarm Communications
During Walk Test [382] Opt. 2
Enables Communication of zone alarms while installer Walk Test is active.
Walk Test End and Begin
Reporting Codes [348], 1
st
and
2
nd
Entries
Access to the reporting codes for Walk Test Begin and Walk Test End.