11 - GENERAL MAINTENANCE AND CLEANING
11.6 Hydraulic Unit (DHW)
For special areas, where water is harder than 200 ppm or 12
grains/ gallon, install polyphosphate dispenser or equivalent
treatment system, compliant with current regulations.
LEGEND
A DHW exchanger xing screw
B DHW priority sensor with lter
C
Boiler/system drain tap (150 unit only)
(C-1 & C-2: access to tap C - bottom of boiler)
D Boiler / system lling tap (150 unit only)
E DHW temperature NTC probe
F Low water cutoff
11.7 Cleaning The Cold Water Filter
Boiler is tted with cold water lter located on DHW hydraulic
assembly (B). To clean:
Drain domestic hot water system. (C - 150 only)
165 Drain is eld supplied/installed.
Remove nut on DHW priority sensor unit using 18mm
wrench. (B)
Pull out ow sensor and its lter.
Remove any impurities.
11.8 Final Commissioning
Allow heating system to heat. Balance the system to
achieve temperature difference across heating supply and
return pipes at the boiler.
Check system for proper volume and pressure. See page 4
for acceptable volume and pressure.
Turn off boiler.
Thoroughly ush water pipe work. Clean lters in heating
return and supply water isolating valves.
Repressurize the system.
11.9 Final Assembly
Place front jacket in position over boiler. Ensure bottom is
located behind the control panel. Secure in position at top
using screws previously removed.
If boiler is to be left in service with the User, set controls
and room thermostat.
If boiler is not to be handed over immediately, close boiler
gas service valve and turn off electrical supply.
If there is possibility of boiler being left during frost
conditions drain boiler and system. See section
11: Component Replacement Or Periodic Cleaning.
Manufacturer recommends attaching a label to the boiler
drawing attention to the fact that the system has been
drained.
Model DCC-150
Model DCC-205
B
A
Hydraulic Assembly (B)
F
E
NOTICE
When replacing and/or cleaning “O-rings” on hydraulic
assembly (DHW), use only Molykote 111 as a lubricant,
not oil or grease.