Loading...
CV3100 series and MINI series high performance general purpose inverter instruction manual
5-6
Function
Code
Name &
Definition
Set Range
Minimun
Unit
Factory
Default
Communi
cation
Address
Modify
P2.35
Reserved
P2.36
Skip freq.1
0.00Upper limit freq.
0.01Hz
0.00Hz
0224H
P2.37
Skip freq.
band 1
0.010.0Hz
0.01Hz
0.00Hz
0225H
P2.38
Skip freq.2
0.00Upper limit freq.
0.01Hz
0.00Hz
0226H
P2.39
Skip freq.
band 2
0.010.0Hz
0.01Hz
0.00Hz
0227H
P2.40
Skip freq.3
0.00Upper limit freq.
0.01Hz
0.00Hz
0228H
P2.41
Skip freq.
band 3
0.010.0Hz
0.01Hz
0.00Hz
0229H
P2.42
Carrier freq.
selection
1.012.0KHz
0.1KHz
022AH
P2.43
Carrier
control
method
0fixed carrier
1automatic adjustment
1
1
022BH
User Managing Interface Parameter
P3.00
LCD language
selection
0Chinese
1English
1
0
0300H
P3.01
Parameter
initialization
0disabled
1revert to factory setting
2: eliminate fault record
1
0
0301H
×
P3.02
Parameter
read-in
protection
0allowed to modify all
parameters (some of which can
not be changed during inverter
running)
1only allow to change the
frequency
2forbidden to modify all
parameters
1
0
0302H
P3.03
Factory
password
09999
1
0
0303H
P3.04
Monitoring
parameter 1
selection
018
1
0
0304H
P3.05
Monitoring
parameter 2
selection
018
1
1
0305H
P3.06
Linear
velocity
quotiety
0.01100.0
0.01
1.00
0306H
P3.07
Close loop
display
quotiety
0.01100.0
0.01
1.00
0307H

Table of Contents