If you do not obey these guidelines your warranty can become void.
CAUTION
If the unit is installed in an IT network, the voltage between neutral and
protective earth during normal operation must be less than 50 V (AC,
RMS), 71 V (AC, peak) or 120 V (DC).
CAUTION
This product can cause a DC current in the PE conductor. Where a
residual current-operated protective device (RCD) is used for protection
against electrical shock, only an RCD of Type B is allowed on the supply
side of this product.
The UPS equipment operating environment must meet the weight requirements
shown in Table 4: UPS cabinet maximum weights, and the size requirements
shown in Table 5: UPS cabinet dimensions.
Table 4: UPS cabinet maximum weights
UPS model Shipping weight
[kg]
Installed weight
[kg]
Floor loading [kg/
m
2
]
93PM G2 50(200) 401 361 456
93PM G2 100(200) 444 404 510
93PM G2 150(200) 487 447 564
93PM G2 200(200) 530 490 619
93PM G2 240(240)
0.9 PF
530 490 619
93PM G2 50(300) 401 361 456
93PM G2 100(300) 444 404 510
93PM G2 150(300) 487 447 564
93PM G2 200(300) 530 490 619
93PM G2 250(300) 573 533 673
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 40 (141)
Eaton 93PM G2 UPS 50 360 kVA User’s and Installation Guide