NOTE: UPS power upgrading is possible only if the sizing of the external cables
is sufficient. Alternatively, the external cabling must be upgraded as well. Fuses
are of the type gG.
Cable sizing is based on the standard IEC 60364-5-52 table B.52.2 and IEC
60364-5-54 table B.54.2. Sizing is for 70 ºC rated copper cables.
Table 11: Rated and maximum currents for rated power and voltage, rectifier
input and UPS output / bypass
UPS model
Rated
voltage [V]
Rectifier input
UPS output /
bypass
Rated current
[A]
Rated
current [A]
Maximum
current [A]
93PM G2 50(200) 380 90 95 76
400 86 95 72
415 83 95 70
93PM G2 100
(200)
380 180 190 152
400 172 190 144
415 166 190 139
93PM G2 150
(200)
380 270 285 228
400 258 285 217
415 248 285 209
93PM G2 200
(200)
380 360 380 304
400 343 380 289
415 331 380 278
93PM G2 240
(240) 0.9 PF
380 360 380 365
400 360 380 346
415 358 380 334