Table 12: Rated and maximum currents for rated power and voltage, rectifier
input and UPS output / bypass
UPS model
Rated voltage
[V]
Rectifier input
UPS output /
bypass
Rated current [A]
Rated
current
[A]
Maximum
current [A]
93PM G2 50
(300)
380 90 95 76
400 86 95 72
415 83 95 70
93PM G2 100
(300)
380 180 190 152
400 172 190 144
415 166 190 139
93PM G2 150
(300)
380 270 285 228
400 258 285 217
415 248 285 209
93PM G2 200
(300)
380 360 380 304
400 343 380 289
415 331 380 278
93PM G2 250
(300)
380 450 475 380
400 429 475 361
415 413 475 348
93PM G2 300
(300)
380 540 570 532
400 515 570 456
415 496 570 433
93PM G2 360
(360) 0.9 PF
380 540 570 547
400 540 570 520
415 537 570 501
NOTE: Maximum rectifier current calculated at the -15% voltage tolerance and
102% continuous overload.
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 48 (141)
Eaton 93PM G2 UPS 50 – 360 kVA User’s and Installation Guide