Table 13: Rated and maximum currents for rated power and voltage, battery
UPS model Battery
Rated current [A] Maximum current* [A]
93PM G2 50(200) 114 139
93PM G2 100(200) 227 277
93PM G2 150(200) 341 416
93PM G2 200(200) 455 554
93PM G2 240(240) 0.9 PF 491 599
93PM G2 50(300) 114 139
93PM G2 100(300) 227 277
93PM G2 150(300) 341 416
93PM G2 200(300) 455 554
93PM G2 250(300) 568 693
93PM G2 300(300) 682 832
93PM G2 360(360) 0.9 PF 736 898
*) Maximum battery current calculated at rated load in the end of discharge of
VRLA battery (1.67 V per cell).
Table 14: UPS power cable terminations
Terminal function Terminal Function
AC input to UPS rectifier X1 L1, L2, L3
AC input to bypass X2 L1, L2, L3
UPS output X3 L1, L2, L3
DC input from external
battery to UPS
X4 battery +, battery -
X5 N
Protective Earth PE PE
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 49 (141)
Eaton 93PM G2 UPS 50 – 360 kVA User’s and Installation Guide