CAUTION
Make sure that prospective short-circuit current resulting at the input
terminals of the UPS is equal or less than conditional short-circuit
current declared on the type plate (and technical specification) of the
UPS. Also make sure that the prospective short-circuit current meets the
minimum requirements listed in Table 18: Minimum required short circuit
current ratings for AC source and battery supply.
Table 18: Minimum required short circuit current ratings for AC source and
battery supply
UPS model Minimum short circuit
current, AC ports [kA]
Minimum short circuit
current, battery port [kA]
93PM G2 xxx(yyy) 4 4
Table 19: Minimum recommended multi-core cable and fuse sizes for battery
connection
UPS model Battery cable, pos. & neg.
line [mm
2
] Battery fuse [A]
93PM G2 50(200) 50 200
93PM G2 100(200) 2 x 50 per pole 315
93PM G2 150(200) 2 x 95 per pole 500
93PM G2 200(200) 2 x 120 per pole 630
93PM G2 240(240) 2 x 185 per pole 700
93PM G2 50(300) 50 200
93PM G2 100(300) 2 x 50 per pole 315
93PM G2 150(300) 2 x 95 per pole 500
93PM G2 200(300) 2 x 120 per pole 630
93PM G2 250(300) 2 x 185 per pole 700
93PM G2 300(300) 2 x 240 per pole 800
93PM G2 360(360) 2 x 185 per pole 1000
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 75 (141)
Eaton 93PM G2 UPS 50 360 kVA User’s and Installation Guide