Outputs Menu
Page 48
Note: An input can be the output of another custom output. However, you can select only
custom outputs of higher number as the custom output you are defining. For example, if
you are defining Custom Output 2, it can use only the outputs of Custom Output 3 and
Custom Output 4 as inputs.
Example
Requirement: To activate a physical output when any of three fire doors (zones 5, 6 and
7) is open, but also shunted.
Solution: Configure a physical output as type Custom Output 1, and configure two custom
outputs as follows.
Input 1 type=Custom Output 2
Input 2 type=Zones Shunted
Input 1 type=Zone Follow (Zone 5)
Input 2 type=Zone Follow (Zone 6)
Input 3 type=Zone Follow (Zone 7)