EasyManua.ls Logo

Eaton Powerware 5125 - Page 28

Eaton Powerware 5125
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION
EATON Powerware
®
5125 (9910-E65) UPS Installation Guide for IBM
®
Applications S 164201698 Rev 1
22
Table 8. Typical Power Connections (Figure 18–Figure 20) (continued)
DescriptionItem
7 PDU to UPS power cord
IBM FC Plug Type Supplier Description
6654 12 IBM Burndy to NEMA L6-30P, 4.3m/14 ft
2972 12 IBM Burndy to NEMA L6-30P, 4.3m/14 ft
2973 12 Eaton Burndy to NEMA L6-30P, 1.2m/4 ft
8 PDU to utility (mains) power cord*
IBM FC Plug Type Supplier Description
6654 12 IBM Burndy to NEMA L6-30P, 4.3m/14 ft
6655 40 IBM Burndy to RS 3750, 4.3m/14 ft
6656 46 IBM Burndy to IEC-309 (P+N+G) 32A, 4.3m/14 ft
6657 PDL IBM Burndy to PDL, 4.3m/14 ft
6658 KP IBM Burndy to KP, 4.3m/14 ft
9 2974 Eaton Burndy to IEC 320-C20, 1.8m/6 ft
10 Output power (UPS to device) cords, located in the E65 accessory kit
Qty. Description
4 IEC 320-C13 to C14, 1.8m (6 ft)
1 IEC 320-C19 to C20, 2.7m (9 ft)
* Other power cords are supported by the PDU. Power cords shown are similar in voltage and amperage to the UPS.
NOTE E65 supports: PDU types 5160 or 9176 with FC 2970; PDU types 5161 or 9177 with
FC 2971.
NOTE E65 does not support iSeries PDU 5162, IEC-309 (3P+N+G) 16A.
NOTE E65 with 2972 or 2973 has a maximum output capacity of 4500 watts even though
IBM PDU 7188 or 9188 can support higher power output. Plan accordingly.

Other manuals for Eaton Powerware 5125

Related product manuals