COMMUNICATION
EATON Powerware
®
9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
53
Mounting Slots
(6 places)
NOTE Matches mounting holes on a single- or
double-gang electrical box.
Cable Exit Openings
for 1/2” Conduit or
Provided Strain Relief
(3 places)
Dimensions are i n mm [inches]
Figure 39. RMP Dimensions
To install an RMP:
NOTE If mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud within the wall.
Do not use hollow wall anchors. The RMP can also be mounted to a single- or double-gang electrical box.
1. If wall mounting, securely mount the RMP. Continue to Step 2.
If desk mounting, install the provided bumpers to the bottom of the RMP
enclosure. Proceed to Step 3.
2. Install 1/2” conduit from the RMP to the IRC through the cable exit openings (see
Figure 39). Proceed to Step 4.
3. Install wiring from the RMP to the IRC using the cable listed in Table 3 and the
provided strain relief bushings in the cable exit openings in the IRC (see
Figure 41) and the RMP.
4. Connect the wiring between the RMP and the IRC plug-in terminal blocks using
terminations shown in Table 3. See Figure 40 and Figure 41 for plug-in terminal
block locations.