EasyManua.ls Logo

Eaton Powerware 9355 - Page 60

Eaton Powerware 9355
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
COMMUNICATION
EATON Powerware
®
9355 UPS (20/30 kVA) Installation and Operation Manual S 164201626 Rev B www.powerware.com
54
Table 3. RMP Wire Terminations
From RMP Terminal To IRC Terminal Remarks
J1-1 J1-1
J1-3 J1-3
J1-4 J1-4
Use Beldon 8690 060 or
e
q
u
i
v
a
l
e
n
t
c
a
b
l
e
J1-5 J1-5
equ
i
va
l
en
t
ca
b
l
e
J1-6
J1-6
5. Install the IRC into an open X-Slot communication bay (see Figure 32 on
page 47).
6. To check the operation of the RMP, ensure that the UPS is supplying the load via
the inverter or bypass. If the indicators on the RMP show the appropriate status,
then it is operating correctly.
If the RMP is not operating correctly, check the wiring, the fuse on the IRC, and
the plug-in terminal blocks for proper seating. If all connections are secure but
the RMP still does not operate correctly, replace the fuse. If this does not correct
the problem, contact your service representative for verification that the RMP is
working correctly.
Plug-in Terminal Block J1 to IRC
NOTE Conduit and wiring
supplied by the customer. The
maximum distance between
the RMP and the UPS is not to
exceed 500 ft (152.4m).
Figure 40. RMP Top Internal View

Table of Contents

Other manuals for Eaton Powerware 9355

Related product manuals