Installation
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
15
Step 2 - Disconnect device and overcurrent protection
1 The socket outlet(s) shall be installed near to the EPS2/EPS5 and shall
be readily accessible.
2 Each socket shall be protected by an overcurrent protection device (a
circuit breaker suitable for Branch Circuits and rated 15A or less).
3 The external circuit breaker(s) must be two-pole type wired in each
conductor, if:
• the ac supply is 2W (see Specifications on page
59), or
• the ac supply is 1W+N but the neutral is not clearly identified.
Procedure complete
Task 2 - Customize EPS2/EPS5
Step 1 - Check position of mounting brackets
EPS2/EPS5s are pre-assembled with 19-inch rack-mounting brackets as
shown in the following diagram. If required, the brackets can be moved to
alternative positions to reduce the effective depth of the unit.
1 Remove top cover.
2 Undo the screws holding each bracket and the module connection
plates.
3 Refit the brackets and plates at the required location. Tighten the
screws.
"
Rack-mounting bracket
#
Module connection plate
$
Alternative position for module connection
plate
%
Alternative position for rack bracket
mounting