EasyManua.ls Logo

Eaton SC200 - Replacing or Adding a Battery Module

Eaton SC200
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
51
Replacing or Adding a Battery Module
Battery modules can be replaced without switching off the dc power system and
disconnecting the equipment it powers.
I
Batteries
Batteries can present a risk of electric shock or burns from high short-circuit current.
Do not alter any battery module cables or connectors.
Do not place any metal objects in or near the connectors.
VRLA lead acid batteries can emit explosive gases and must be installed with adequate
ventilation. Do not install batteries in a sealed room or cabinet.
Do not attempt to disassemble battery modules. Return them (in their original packaging) with a
completed Equipment Incident Report on page
71.
Only dispose of battery modules according to Battery Disposal and Recycling on page 55.
Check the battery recharge dates on the shipping carton labels. Do not use the batteries if the
date has expired and the batteries were never recharged. Contact your battery supplier.
Batteries are heavy. Two people may be required to lift a module.
Batteries must be installed at the bottom of the rack.
Removing a Battery Module
Step 1 - Switch off battery circuit breaker
Step 2 - Disconnect cables
Disconnect the battery module cable(s).
Step 3 - Undo rack screws
Step 4 - Pull out the battery module
The battery modules are heavy (54.9kg/121 lb). A minimum of two
people are required to lift a module.
Step 5 - Replace battery module or reconnect cables
Either:
Insert a replacement battery module into the empty position (see details in
following section), or
Reconnect the cables and switch on the battery circuit breaker.