Start-Up
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
33
Step 2 - Systems without batteries connected
Ignore this Step if the EPS2/EPS5 system has batteries connected.
1 In the SC200 or SC100 configuration file, set the battery capacity to zero
(to indicate no batteries are connected):
Either:
On SC100 go to: Menu > Configuration > System > Edit > Battery
Capacity >Edit, or
On SC200 go to: Battery > Battery > Battery Capacity.
Set Battery Capacity to zero.
2 Disable the Temperature Compensation control process (this is only
required when batteries are connected):
Either:
On the SC100 go to: Menu > Configuration > Temp Compensation >
Edit, or
On SC200 go to: Control Processes > Temperature Compensation >
Enabled.
Select Disable.
3 Change Float Voltage (dc output voltage) if required:
If required, the Float Voltage (dc output voltage) can be adjusted
within the Output Voltage range in the Specifications on page
59.
Refer to the SC200 or SC100 system controller System Controller
Operation Handbook for details on how to adjust the Float Voltage.
Also adjust the alarm voltage settings (Low Load, Low Float, High
Float and High Load).
Step 3 - Setup communications (if required)
For an overview of communications options see External Communications on
page
7.
To configure the communications settings refer to Communications Options in
the System Controller Operation Handbook (see Related Information on page
i).
Procedure complete