Maintenance
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
57
Step 4 - Download the configuration file
1 Connect to the system controller with DCTools. See details on page
39.
2 If a copy of the old configuration file, or a master configuration file is
available, then use DCTools to restore (download) it to the new system
controller.
See Backup and Restore on page 36.
If you receive an error message about the MIB file version, please contact
your Eaton dc product supplier for advice.
3 If a copy of the old configuration file, or a master configuration file is not
available, then use the keypad or DCTools/Web to change the configuration
settings to the correct values (provided the system controller is set for the
correct nominal system voltage).
Step 5 - Check the system controller operation
1 Map the I/O board (SC200 only):
In DCTools/Web go to: I/O Board > I/O Board to Serial Number Mapping.
Copy the I/O board serial number(s) from the RXP Bus Slaves table to
the I/O Board to Serial Number Mapping table to map an IOB Number to
each I/O board (overwrite an existing serial number if required).
2 Check that the system controller has registered all rectifiers.
3 Check all control processes, alarms and current measurement(s).
4 Check the power system identification parameters and communications
settings.
5 Change the configuration file as required to ensure that the system
controller operates as intended.
6 Check the system controller time (SC200 only). See details in system
controller handbook.