EasyManuals Logo

Eaton SPD Series Installation Manual

Eaton SPD Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
40 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09
CChhaapptteerr 66 SSPPDD DDiissppllaayy RRoottaattiioonn
The SPD display can be rotated on the SPD enclosure, up to 360 degrees. This allows you to position the
display for the best visibility regardless of the position in which the SPD is installed.
Rotations are at 90, 180, and 270 degrees.
Reposition the SPD display as follows:
1. Remove power from the unit.
2. Remove and discard the perforated overlay material at the two opposite corners of the display.
3. Remove the two Phillips head screws that hold the display.
4. Rotate the display to the desired position. Be careful not to overstress the display ribbon cable.
5. Place the display back onto the SPD enclosure. Be careful not to overstress or crimp the ribbon cable.
6. Replace the two Phillips head screws. Tighten screws to 1.35 Nm (12 in-lbs).
7. Restore power to the unit.
SPD Display Rotation

Table of Contents

Other manuals for Eaton SPD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SPD Series and is the answer not in the manual?

Eaton SPD Series Specifications

General IconGeneral
TypeSurge Protective Device
Voltage Rating120/240V, 208Y/120V, 480Y/277V
Surge Current CapacityUp to 200kA
Modes of ProtectionL-N, L-G, N-G
Operating Frequency50/60Hz
CertificationsUL 1449
SPD TypeType 1, Type 2
Maximum Surge CurrentUp to 200kA
Nominal Discharge Current (In)10kA, 20kA
Short Circuit Current Rating (SCCR)Up to 200kA
Enclosure TypeNEMA 1
MountingPanel Mount
StandardsUL 1449, IEEE C62.41
DiagnosticsVisual Indicators
Remote MonitoringOptional
Maximum Discharge Current (Imax)Up to 200kA