EasyManua.ls Logo

Eaton SPD Series - 7 IEC Approved Models

Eaton SPD Series
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09 41
CChhaapptteerr 77 IIEECC AApppprroovveedd MMooddeellss
Eaton’s one-port low-voltage surge protective device delta models SPD120480D3M, SPD160480D3M and
SPD200480D3M meet the requirements of IEC 61643-11 / EN 61643-11, Part 11: Test Class II, and are
intended to be installed in applications with a degree of protection rated IP 20.
The delta models are intended for use with a three-phase TN-S system with PE and neutral distribution, 5
conductor with a minimum 10 AWG or 6 mm
2
. The delta models are also intended for use with a three-phase
TN-C system with PEN distribution, 4 conductor with a minimum 10 AWG or 6 mm
2
. Screws used for
connection to ground shall be #10-32 x 3/8” and shall not be zinc or aluminum. This product is not serviceable
and contains no replacement parts..
Additional product information and ratings for IEC applications:
The SPD contains internal disconnects with a short circuit current rating I
SCCR
of 200kA.
Residual current IPE for this product is 5 mA.
Operating temperature is normal -5°C to 40°C (23°F to 104°F).
Humidity range is 5% through 95% non-condensing.
The SPD may be mounted directly to earthed conductive surface, installed as per this manual.
Temporary overvoltage rating UT = 402.6 V.
Withstand or safe failure mode, for tT = 120 minutes, UT = 526 V.
Modes of protection as marked on a wye SPD = L - L, L - N, L - G(PE), N - G(PE). Modes of protection as
marked on a delta SPD = L - L, L - G(PE).

Table of Contents

Other manuals for Eaton SPD Series

Related product manuals