Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09 41
CChhaapptteerr 77 IIEECC AApppprroovveedd MMooddeellss
Eaton’s one-port low-voltage surge protective device delta models SPD120480D3M, SPD160480D3M and
SPD200480D3M meet the requirements of IEC 61643-11 / EN 61643-11, Part 11: Test Class II, and are
intended to be installed in applications with a degree of protection rated IP 20.
The delta models are intended for use with a three-phase TN-S system with PE and neutral distribution, 5
conductor with a minimum 10 AWG or 6 mm
2
. The delta models are also intended for use with a three-phase
TN-C system with PEN distribution, 4 conductor with a minimum 10 AWG or 6 mm
2
. Screws used for
connection to ground shall be #10-32 x 3/8” and shall not be zinc or aluminum. This product is not serviceable
and contains no replacement parts..
Additional product information and ratings for IEC applications:
The SPD contains internal disconnects with a short circuit current rating I
SCCR
of 200kA.
Residual current IPE for this product is 5 mA.
Operating temperature is normal -5°C to 40°C (23°F to 104°F).
Humidity range is 5% through 95% non-condensing.
The SPD may be mounted directly to earthed conductive surface, installed as per this manual.
Temporary overvoltage rating UT = 402.6 V.
Withstand or safe failure mode, for tT = 120 minutes, UT = 526 V.
Modes of protection as marked on a wye SPD = L - L, L - N, L - G(PE), N - G(PE). Modes of protection as
marked on a delta SPD = L - L, L - G(PE).

Table of Contents

Other manuals for Eaton SPD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SPD Series and is the answer not in the manual?

Eaton SPD Series Specifications

General IconGeneral
TypeSurge Protective Device
Voltage Rating120/240V, 208Y/120V, 480Y/277V
Surge Current CapacityUp to 200kA
Modes of ProtectionL-N, L-G, N-G
Operating Frequency50/60Hz
CertificationsUL 1449
SPD TypeType 1, Type 2
Maximum Surge CurrentUp to 200kA
Nominal Discharge Current (In)10kA, 20kA
Short Circuit Current Rating (SCCR)Up to 200kA
Enclosure TypeNEMA 1
MountingPanel Mount
StandardsUL 1449, IEEE C62.41
DiagnosticsVisual Indicators
Remote MonitoringOptional
Maximum Discharge Current (Imax)Up to 200kA