Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09 19
CChhaapptteerr 55 PPoowweerr XXppeerrtt SSPPDD UUsseerr SSeettuupp
55..11 GGeenneerraall
The Eaton Power Xpert SPD can be set up using just the local display or with a laptop, CAT5e cable and a web
browser. Modbus, BACnet, and HTTP are initially disabled to provide cybersecurity protection. Modbus can be
enabled through the LCD module or the web UI. BACnet and HTTP can only be enabled through the web UI.
The PX-SPD must be rebooted after enabling Modbus or BACnet communications.
55..22 SSeettuupp UUssiinngg OOnnllyy tthhee LLooccaall DDiissppllaayy
Once the SPD has been powered up the device’s home screen will appear on the local display. See below. The
home screen shows the catalog number of the device, the device’s name, the time and the firmware revision.
FFiigguurree 2211.. PPoowweerr XXppeerrtt HHoommee SSccrreeeenn
55..22..11 SSeettttiinngg UUpp tthhee DDaattee aanndd TTiimmee
To set the current date and time:
1. Press Enter to go to the main menu.
FFiigguurree 2222.. PPoowweerr XXppeerrtt MMaaiinn MMeennuu
2. Scroll down the menu to settings by pressing the down arrow button. The cursor “<” is located to the
right of the menu category selection. Position the cursor to the right of settings< by pressing the Down
button twice and then press Enter.