input is cleared.
Send Alert Enables the system to send an
alert when the input has been activated.
Send Update Log Enables the system to log
when this input is activated.
Activation Delay Congures time delay from
when the input detects the active state to
when the action programmed in the Type
section is performed by the system. For
example, if you connect a door sensor to the
input and program a 5 minute activation
delay, the door will need to open and remain
open for 5 minutes before the thermostat
takes action.
Deactivation Delay Congures a time delay
from when the input detects the inactive
state to when the system reverts back to its
normal operating conditions. For example, if
you connect a door sensor to the input and
program a 5-minute deactivation delay. The
door will remain closed for 5 minutes before
the thermostat will revert back to the normal
operating condition.
Min Action Duration Congures the
minimum amount of time the system will
perform this action. This timer will run its
course regardless of whether the input has
reverted back to its normal state and the
deactivation timer has expired. This option
is useful for applications where you want
to run a device (i.e., fan or compressor) for
a minimum amount of time after the input
has been activated rather then using the
deactivation delay. This ensures the fan or
motor does not short cycle.