Functional description of 3-LCD controls and indicators (see Figure 2-1)
Index
Control or
indicator Functional description
19 Supvr Button / LED Pressing the Supervisory button places the contents of the
Supervisory queue onto the display screen for review. Active
supervisory events are displayed in the order in which they are
received. When a supervisory event is highlighted on the display,
pressing the Supervisory button acknowledges the event and
advances the display to the next event.
The Supervisory LED serves as a common supervisory event
indicator. The LED, when flashing, indicates that there is an
event in the queue that has not been reviewed (local systems) or
acknowledged (proprietary systems). When on steady, the LED
indicates that all events in the queue have been reviewed or
acknowledged.
Note: Security events allow for multiple activations from the
same point. It is not uncommon for this to happen.
20 Alarm Silence
Button / LED
Pressing the Alarm Silence button turns off the EVAC and
ALERT channels, and all active audible and visible notification
appliance circuits. Pushing the button a second time turns the
notification appliance circuits back on. This button may be used
to cancel the drill signal.
The Alarm silence LED, when lit, indicates that the active
notification appliance circuits have been silenced.
Notes
• Project configuration settings affect Alarm Silence function
operation
• Pressing the Alarm Silence and Panel Silence buttons at the
same time actives the panel lamp test function
21 Reset Button / LED Pressing the Reset button activates the system’s reset sequence
to restore the system to normal.
The Reset LED flashes quickly during the smoke power-down
phase, flashes slowly during the power-up phase, is on steady
during the restoral phase, and is off when the system has reset.
Notes
• The Reset button is disabled as long as the alarm silence
inhibit timer is running
• The Reset button does not affect disabled points or manually
overridden functions
• The Reset button may not affect security or access control
devices. These points may be included in the supervisory or
monitor display queues.