3-LCD operating instructions
EST3 System Operation Manual 2.19
Guard patrol groups
Guard patrol groups are used to monitor the activities of security
guards. A security guard can be required to walk any one of a
number of predetermined tours. During each tour, the guard
must activate guard patrol stations that are located along the
tour.
When a guard activates a station too early, too late, or out of
sequence, the 3-LCD displays a Guard Patrol Active message in
the alarm message queue. The operator can press the Details
button to determine which station reported in.
Starting a guard patrol
Activating a guard patrol group starts the system’s early, late,
and out of sequence sensing mechanisms. If a station reports in
early, late, or out of sequence, the guard patrol sensing
mechanisms stop and the tour is ended.
To activate a guard patrol:
1. Press the Command Menus button , then choose Activate.
2. Choose Guard Patrol Route.
3. Select the guard patrol route from the list.
4. If prompted, enter a valid user access level password.
Restoring a guard patrol
When a guard patrol tour ends because a guard patrol station
was not activated at the proper time, you must restore the Guard
Patrol group to which the station belonged.
To restore a guard patrol:
1. Press the Command Menus button then choose Restore.
2. Choose Guard Patrol Route.
3. Select the guard patrol route from the list.
4. If prompted, enter a valid user access level password.