3-LCD operating instructions
2.20 EST3 System Operation Manual
Check-in groups
Check-In groups are used to monitor occupants in nursing care
facilities. Occupants must activate their check in device during
their assigned check-in period. The 3-LCD displays a Check-In
Active message for any member of a group that fails to check in
on time. Activating a check-in device anytime outside the check-
in period or a second time within the check-in period sends an
Emergency Active message to the 3-LCD display.
Activating a check-in group
Activating a check-in group starts the group’s check-in
sequence. The 3-LCD displays a Function Active, Check-In
Activate event to signal the operator that a check-in timer has
started. If every member of the group checks in, the group
automatically restores after the time-out period expires, and the
panel returns to normal operation.
If any member fails to check in, a Check-In Group Activate
event is generated for each failed check-in. Again, the Check-In
function will automatically restore upon expiration of the time-
out period.
Note: Normally time controls are used to activate check-in
groups. you can also use the Enable command to activate a
check-in group.
To activate a check-in group:
1. Press the Command Menus button , then choose Activate.
2. Choose Check-In Group.
3. Select the group from the list.
4. If prompted, enter a valid user access level password.
Canceling a check-in sequence
You cancel a check-in sequence by restoring the check-in group
before the check-in timer expires.
To cancel a check-in sequence:
1. Press the Command Menus button , then choose Restore.
2. Choose Check-In Group.
3. Select the check-in group from the list.
4. If prompted, enter a valid user access level password.