7.3.1 Calibration wizard for voltage measurement inputs Uc, Uk, Ul, Um.
To open window Calibration SA10A see 7.3 Recalibration procedure.
Select tab Analog inputs in the window Calibration SA10A.
Click on button Calibration wizard.
The following window is displayed.
• Calibration wizard. Step 1.
Select a single analogue input or all analogue inputs to calibrate
with the option buttons
If all voltage channels shall be calibrate at the same time the
same voltage source must be connected to all selected voltage
inputs
Press the command button ”Next”.
• Calibration wizard. Step 2
Connect a stable DC-voltage source and a voltage instrument to
the selected inputs.
For more information about connections see.
7.2.1 Check voltage measurement inputs Uc, Uk, Ul, Um.
Click the command button. Next.