EMC INDUSTRIAL GROUP LTD Internal Signals
MW61A_IM_ALL_SV6.09d_en 30/47
Limit 3
Q23531 limit 3 source (modbus address of signal) 8340, g7
Q23532 limit 3 mode 8344, g7 fill control = 4
Q23533 limit 3 delay 8342, g7 0.00 s
Q23534 setpoint 3H 8334
Q23535 setpoint 3L 8346
Events/Alarms/Faults
Various events can be triggered by the inputs (eg to capture the weight) or automatically when certain
situations are detected by the transmitter. Each event has an ID and produces a value.
Q2361 event ID 8780, g8
ID of most recent event.
Q2362 event value 8782, g8
Value of most recent event.
Q2363 last alarm event 8784, g8
Value of most recent event.
Q2364 alarm list (press EDIT to view list of all possible alarms) 8920, g8
Scroll through a list of all possible alarms.
Q2365 delay time [0.00 to 300.00] 8458, g8 0.00 s
A timer used by the macros.
Q2366 healthy options 8456, g8 0
Selects which faults control the healthy signal.
Q2368 captured weight 8786 kg,t,g
On the rising edge of a ‘capture weight’ input signal, the weight is captured and recorded here.
Q2369 fault options 8454
Allows selected faults to not raise an alarm.
Memory Storage
Memory storage is used to save or recall a group of settings to memory. This can for example be used
to save different settings that change for different products. The instrument can store up to 20 groups
of settings.
Memory Setup
Q23811 memory usage 8680, g8 0
Selects how the memory will be used. Several preset choices are available or it may be set for a custom
setup.
memory usage
description default memory store name
0 disabled
1 custom
2 setpoint 1 PRODUCT
3 setpoints 1 & 2 PRODUCT
4 loadcell calibration CALIBRATION
5 not used
6 not used
Q23812 data 1 source 8670, g8 0
Q23813 data 2 source 8672, g8 0
Q23814 data 3 source 8674, g8 0
Q23815 data 4 source 8676, g8 0
The four items above contain the addresses of settings that will be stored in the group memory. The
addresses can only be set if the memory usage is set to ‘custom’.
Q23810 memory store name 3600, g8
This sets a name for the memory store. If a text name is entered, it will replace the word ‘GROUP’ in
the following memory settings.